StacksVerified U.S. federal law reference

40 CFR Part 60, Table 3 — Municipal Waste Combustor Operating Guidelines

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
Municipal waste combustor technologyCarbon monoxide emissions levels (parts per million by volume) aAveraging time (hrs) b
Mass burn waterwall1004
Mass burn refractory1004
Mass burn rotary refractory10024
Mass burn rotary waterwall25024
Modular starved air504
Modular excess air504
Refuse-derived fuel stoker20024
Fluidized bed, mixed fuel (wood/refuse-derived fuel)200c 24
Bubbling fluidized bed combustor1004
Circulating fluidized bed combustor1004
Pulverized coal/refuse-derived fuel mixed fuel-fired combustor1504
Spreader stoker coal/refuse-derived fuel mixed fuel-fired combustor20024
Semi-suspension refuse-derived fuel-fired combustor/wet refuse-derived fuel process conversion250c 24
Spreader stoker fixed floor refuse-derived fuel-fired combustor/100 percent coal capable250c 24

a Measured at the combustor outlet in conjunction with a measurement of oxygen concentration, corrected to 7 percent oxygen, dry basis. Calculated as an arithmetic average.

b Averaging times are 4-hour or 24-hour block averages.

c 24-hour block average, geometric mean.

[71 FR 27334, May 10, 2006]